SBN341N 3P 40A Switch
Technical Characteristics close all Architecture Number of poles: 3 P Type of pole: 3 P Main electrical features Frequency: 50/60 Hz Rated operational voltage Ue: 230/400 V Voltage Rated insulation voltage: 440 V Rated impulse withstand voltage: 6000 V Electric current Rated operational current in AC21 category A: 40 A Rated operational current in AC21category B: 40 A Acceptable current rating with AC22 category A: 40 A Acceptable current rating with AC22 category B: 40 A Rated short-time withstand current 1s: 0,6 kA Thermal rated current outside of housings: 40 A Power Power loss per pole at In: 1,1 W Total power loss under IN: 3,3 W Endurance Electrical durability at nominal load in AC21in operating cycles: 5000 Electrical durability at nominal load in AC22 in operating cycles: 5000 Number of mechanical operations: 60000 Dimensions Depth of installed product: 68 mm Height of installed product: 83 mm Width of installed product: 52,5 mm Installation, mounting Tightening torque: 2,8Nm Connection Cage clamp position: in line Connection cross-sect. rigid cable: 2,5 / 25mm² Connection cross-sect. flexible conductor: 2,5 / 16mm² Type of connection: with screw Standards European directive WEEE: not concerned Safety Protection index IP: IP20 Use conditions Degree of pollution according to IEC 60664 / IEC 60947-2: 2 Altitude: 2000 m Storage temperature: -40 to 80 °C Identification Device family: SBN